Voltage AC (Un) 5~1000V DC
Auxiliary Supply 85~300V AC (default) or 9-60V DC
Current Range 0~2000A
DC Shunt Input 75mV in default, 60mV, 45mV optional
Power consumption ≤ 2W
AC voltage withstand 4400V/ 1min
Impulse voltage withstand 6.4kV - 1.2/50μS waveform
Pulse output Configurable, default at 1000imp/kWh
Pulse duration Configurable: 60/100(default)/200ms
Pulse type Total kWh/ import kWh/ export kWh
Display LCD with backlit
Max. Reading 999999.9kWh
Weight 220g
Standard GB/T 33708-2017
Unit Characteristics
The Unit can measure and display:
Pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.
Shunt Primary Current
The unit can be configured to operate with primary current and secondary input.
Primary current range: 0~2000A.
Second input: 75mV in default, 45mV, 60mV optional
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:
Baud rate 1200,2400, 4800, 9600,19200 bps
Parity none (default)/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu.
Set-up screens are provided for setting up the RS485 port.
Pulse output
The unit provides a pulse output. The constant can be configured to below:
1000 imp/kwh
100 imp/kWh
10 imp/kWh
1 imp/kWh
Pulse width: 200/100(default)/60 ms.
Note: the relationship between pulse constant and CT1
CT1 setting | Default pulse constant | Settable pulse constant |
1 – 20 | 1000 imp/kWh | 1000,100,10,1 imp/kWh |
21 – 200 | 100 imp/kWh | 100,10,1 imp/kWh |
201 – 2000 | 10 imp/kWh | 10,1 imp/kWh |
*when the CT setting on meter is 2000A, the default pulse constant is 10 imp/kWh and it can be set to 10 imp/kWh or 1 imp/kWh.
*Over-current alarm: Alarm will happened when the current is over the CT1 value set on the meter. The Alarm LED will stay solid and the corresponding register value will be changed. The user can read this register through communication to determine whether an overcurrent alarm has occurred.
The pulse outputs can be set to generate pulses to represent Import kWh/ Export kWh/ total kWh.
The pulse output is passive type, complies with IEC62053-31 Class A.
Voor technische vragen: info@kwhmeter.nl of 06-50244649
Voor algemene vragen: sales@kwhmeter.nl of 06-45737811
1 fase kwh meters
3 fase kwh meters
Mid gekeurde meters
Multi functionele meters
KWH meters zonnepanelen
DC meters
Stroomtrafo's
E&S Electrading B.V.
Jan van Banningstraat 2-b
2381 AV Zoeterwoude
KvK: 78386497
BTW: 861370363B01